S-FLS-2-24.Ex

This SPD limits induced transients of different origin (lightning stroke, switching impulse, etc.). This is achieved by diverting the transient current to ground and limiting the signal line voltage to a safe level for the duration of the surge. It can be applied to 2-wire pressure transmitter, valve positioner, electrical converter, flowmeter, solenoid valve and other field instruments and FF, PROFIBUS PA ect.

Type

Wire system

Ex

Ground protection

Share
S-FLS-2-24.Ex

【核心技术】

S-FLS介绍.jpg

【安装与拆卸】



15719913382876999Yxm.gif1571991347588242JgtX.gif

                                    

安装                                                                      拆卸


General parameters
Nominal voltage Un 24 V
Max. continuous operating voltage Uc(DC) 32 V
Max. continuous operating voltage Uc(AC) 22.5 V
Nominal current IL 600 mA
Series impedance 1.8 Ω
Response time Ta < 1 ns
Bandwidth fG(100 Ω resistance) 10 MHz
雷电参数
Total lightning impulse current Iimp(10/350 μs) ,D1 5 kA
Lightning impulse current Iimp(10/350 μs) ,D1 2.5 kA
Max. discharge current Imax(8/20 μs) ,C2 20 kA
Nominal discharge current In(8/20 μs) ,C2 10 kA
Voltage protection level Up(8/20 μs) ,C2 L – L ≤ 60 V/ L – PE ≤ 600 V
Voltage protection level Up(1 kV/μs) ,C3 L – L ≤ 45 V/ L – PE ≤ 600 V
Operating conditions
Operating temperature -40 ℃ ~ +80 ℃
外壳材料
Material PC
Flame retardant grade(UL94) V0
Protection degree IP20
Mechanical specifications
Connecting wire size 0.2 mm2 ~ 2.5 mm2
Installtion 35 mm DIN rail
Grounding mode Rail/ terminal (optional)
Certified data
Standards IEC 61643-21/GB/T 18802.21
Product approvals CNEX, SIL, CE, FCC, CCC
Device type Type A
HFT 0
Operating mode Low / high
SIL SIL3
λS (1 FIT=10-9/h) 9.40 FIT
λDU (1 FIT=10-9/h) 0.464 FIT
λDD (1 FIT=10-9/h) 0 FIT
λTOTAL (1 FIT=10-9/h) 9.864 FIT
SFF 95.3%
PFDavg(T1=1Y) 2.03E-06
PFH 4.60E-10 1/h
Intrinsically safe circuit certification Ex ia ⅡC T6 Ga
Ui 30 V
Ii 50 mA
Pi 375 mW
Ci 0 μF
Li 0 mH